Bizator  /  Adverts  /  equipment and materials  /  industrial equipment  /  electrical survey units

Measuring transducer AC voltage Е855/3-M1

Offer type: salePublished: 05.02.2019
Price:1 000 UAH
Company:Lispriborservis
Seller:Ivan Valer'evich
Phones:
Show phone
Write a message
Address:Ukraine, Luhans'ka Oblast', Syevyerodonets'k
Intended for transformation of alternating current or AC voltage into a unified DC signal.
The measurement range of the transformed input signals:
voltage 0-125V 0-250V 0-400V 0-500V
Measuring range of output signals:
Current 4mA-20mA
The range of load changes: 0-0,5 kOhm
Maximum permissible reduced basic error of ±0,5%
 
Measuring converters of AC voltage Е855/3-M1 is designed to convert alternating current or AC voltage into a unified DC signal.
Used to control current and voltage electrical systems and installations of complex automation of power facilities, power-control system of objects of different industries. Information is the mean value of the output signal.

Main technical data
 
Measuring range the output signal is 4mA-20mA
The range of load changes - 0-0,5 kOhm
voltage - 0-125V;
The frequency of the AC circuit - 45-65Hz

Maximum permissible reduced basic error of ±0,5% of the fiducial value of the output signal for all converters.
The output signal is directly proportional to the RMS (current) value of the input signal.
The settling time of the output signal is not more than 0.5 s.
Power supply voltage 220(240)V, frequency 50 (60)
The power consumed from the circuit input signal does not exceed: 0,5 VA – Е855/3-M1, from the food chain 4B·A.

Operating conditions :
ambient temperature - from -30° C to +60° C.
relative humidity from 80% to 95% at 35°C
Dimensions - 125х110х100 mm.
Weight - not more than 0.7 kg.

In stock - 1pc.