Furnace automatic combustion Siemens LGB 22.330A27

Offer type: salePublished: 19.03.2016
Company:TD Favorit
Seller:menedzher
Phones:
Show phone
Write a message
Address:Ukraine, Kyiv
Automatic combustion LGB22.330A27 is designed to control one or two stage gas or combined gas/oil burners of small to medium capacity (typically up to 350кВт) with/without fan with intermittent operation.

Automatic combustion LGB22.330A27 is used to start and control one - and two-stage gas or combined gas/oil burners with intermittent operation.
Depending on the type of the automatic firing device (hereinafter the device) the flame is monitored either by using the ionization electrode, the flame sensor blue QRC1...for gas/oil blower burners, or using UV sensor QRA...(with auxiliary unit AGQ1...A27).
Complete with the appropriate adapters machines of the combustion type LGB.. replaces the previously produced types LF17 ... and LFM1...(please note the section "Types of modifications" in Chapter "Ordering").

- Machines for burning air-blast burners with gaseous fuel according to EN676
- Machines the combustion gas burner according to EN298
- Definition of insufficient voltage
Control of air pressure along with the functional check of air pressure switch during startup and operation
- Possibility of remote electrical re-launch
- LGB41... for use with atmospheric gas burners

Machines burning for pre-purging with nominal load air volume and control of actuator.

Property

The value

Flame detector

Ionizer. probe (ION) or UV detector QRA... with AGQ1 A27...

Type

LGB22.330A27 5)7)

tw/~*

9

t1/min.

30

TSA/s max.

3

t3n/~

2.4 GHz

t3/~

3

t4/~

8

t9/6) max.

---

t10/min.

4

t11/3) max.

12

t12/3) max.

11

t20/~

2


tw wait Time 1) On request
- t1 is the Time to purge 2) For atmospheric burners with power up to 120 kW
- TSA Safe ignition timing 3) Max. the response time allowed for the drive
- t3 is the Time to ignition 4) is Also used for steam generators
- t3n Time after ignition 5) Also applies for the stationary air heaters
- t4 Interval "BV1-BV2" or "BV1-LR" 6) "t9" + time relay flame
- t9 safe the Second time (only for LGB41...) 7) Also available for AC 100...110 V; in this case, the last 2 digits 27 should be replaced by 17
- t10 Specified time for the alarm air pressure
- t11 Programmed opening time of actuator "SA" 8) Without inner microprogrammes (MPR.); can only be used with external MPR. 6.3 A (slow-blow)!
- t12 Programmable opening time of actuator "SA"
- t20 Interval until the automatic closing mechanism for programming