The high voltage meter constant and AC RD-250
Familiarizes you with device technical data and principle of operation of the meter high voltage RD-250 to the extent necessary to operate and maintain it in permanent readiness for operation.
Staff should have the tolerance to operate in electrical systems with voltages above 1000 C.
Product purpose
The high voltage meter AC / DC RD-250 (
further - meter) is designed to measure AC sinusoidal
voltage frequency of 50 Hz from 20 to 230
kV and DC voltage from 20 to 230 kV.
RD-250 provides a measurement with high
accuracy:
· the effective value of alternating voltage frequency of 50 Hz;
· average permanent voltage.
RD-250 can be used in test high voltage laboratories of electrical engineering and energy profile, as well as research institutions.
The performance of the products complies with GOST 17512-82, climatic category UHL 4.2 according to GOST 15150-69 and group 2 devices according to GOST 22261-82.
Conditions use of the product
RD-250 designed for operation in the following conditions:
· indoors or under a shed in the absence of shaking, vibration, fumes corrosive liquids;
· ambient temperature, °C - from 10 to 35 °C;
· relative humidity the ambient air, % - up to 80;
· atmospheric pressure, kPa (mm RT. Art.) - 84 - 106,7 (630-800);
· the coefficient of nonsinusoidal the measured AC voltage should be no more than 8%;
·
ripple measured
the DC voltage should not be
more than 1%;
· the distance from high voltage unit RD-250 - BV to conductive objects that are grounded or are under the capacity - not less than 2 m;
Main technical data
Name
Rated value
Results metrological certification
1
2
3
1 Range measurement of DC voltage (average value), kV
from 25 to 250
2 Range measurements of the AC voltage (root mean square), kV
from 15 to 175
·
3 Range frequency when measuring AC voltage, Hz
from the total of 47.5 to 52.5
4 Input the resistance of the high voltage unit RD-250 - BV DC, IOM
1200±20
5 Input the resistance of the high voltage unit RD-250 - BV alternating current frequency of 50 Hz, MOhm, not less
600
6 Limits permissible relative error when measuring voltage constant current, %
±3
7 Limits permissible relative error when measuring AC voltages current, %
±3
8 Resolution reference kV
0,001
9 Power NI and MI made from built-in Ni-MH batteries size AA voltage of 1.2 V and a capacity of 1.6-2.1 a∙h:
· voltage power, In -
·duration of continuous operation without recharging, h, not less
5±0,2
8
10 Range the action of the channel, m, not less
5
11
Duration
continuous operation
RD-250 at the maximum input
voltage, h, not more
1
12
Duration
continuous operation
RD-250 when the input voltage up to 150
kV, h, not more
8
13 Time to establish the operating mode after power-up, minutes,
1
14 Overall dimensions, mm, not more:
·
RD-250 - NI in
working position
· RD-250-MI
· the box laying
height -1825;
size :
on the screens- Ǿ530;
on the supports- Ǿ1070
HH
HH
The warranty period is 1 year.
The apparatus metrologically certified.
Number of deliveries: any.
http://dneproenergotehnologii.pul.ru, http://det-etl.n4.biz
http://dneproenergo.uaprom.net, http://det.zakupka.com
+38 (095) 601-35-90, (056) 788-51-01, (092) 788-51-01
SKYPE: energo-CL