General information about leakage relay RU-1140
Price: | negotiated |
Company: | Strojmash,PAO |
Seller: | Vasilij |
Phones: | (050)4523230 Show phone |
Address: | Ukraine, Donets'ka Oblast', Makiyivka |
Leakage relay
RU-1140 designed to protect people from electric shock and
other hazardous effects of the leakage current to earth in electrical networks
voltage 1140 In isolated transformer, used in
underground coal mines and mining enterprises in the conditions of cold,
temperate and tropical climate.
The relay consists of a block breaker OIE-1140 and block
compensate for capacitive currents and bypass the faulted phase BKZ-1140. Block
BSO-1140 is designed for continuous monitoring active
insulation resistance and leakage all under the operating voltage of the network and
enable disable switching apparatus while reducing
these resistances lower normalized values, as well as to control
insulation resistance of the three phases of the network relative to the ground when disabled
switching device and prevent its inclusion by reducing
insulation resistance and leakage to the value equal to the resistance of the actuation
mode warning control and lock. Block BKZ-1140 is designed
to bypass the faulted phase to earth and compensate for capacitive currents
a leak. RU-H:
R - relay;
In - leakage;
1140 - voltage;
X5 - the type of climatic performance (HL, T5) according to GOST 15150-69
and GOST 15543-70.
Conditions
Height over
sea level is not more than 1000 m
Ambient temperature from -10 to 60°C.
Relative humidity up to 98% at 25°C in
conditions of temperate and cold climate and 60°C in conditions of tropical climate;
in the mines, including hazardous gas and dust.
In terms of safety relays comply with GOST
22929-78.
For the needs of national economy and export supply relay
meet TOO.48.081-79. THE 12.48.081-79
Specifications
View
explosion protection output circuits of preventive control and lock
disconnected from the controlled network according to GOST 12.2.020-76 - And the Degree of protection relays
(except input terminals) according to GOST 14254-80 - IP54 rated supply voltage
three phase power supply frequency of 50 Hz, A - 1140 Permissible voltage fluctuations
supply network - from 0.85 to 1.1 ur power consumption, V·a, not
more: unit BSO-1140 - 100 block BKZ-1140 - 60 Number of contacts output
relay, at least: block BT-1140 - 1P., 2H., 1P. block BKZ-1140 - 3s. Most
DC switching contacts of the output relay unit BSO-1140, when
a voltage of 250 V and resistive load, And - 0,30 Alternating current, switched
the contacts of the output relay block BKZ-1140, when the voltage from 220 to 1000 V,
frequency from 50 to 1100 Hz and an active load, And from 0.03 to 0.30 Valid
the change in network capacity, µf per phase from 0 to 1.0 Resistance actuation
unit BSO-1140: single-phase leakage: for basic protection, Ohm, not more than 50
for backup protection, com - 28 to 35 for a symmetrical three-phase
leak, ohms per phase, not less than 60 mode warning control and
lock % resistance from tripping for single-phase leakage, no less -
150 Resistance actuation unit BKZ-1140, kom, no less - 4,0 Own
the response time of the unit BSO-1140: when the voltage at the network terminals
to 0.6 of the nominal value, due to the occurrence of the interfacial
arcing faults with arc touch the walls of the shell of electrical equipment, not
more of 0.10 when the resistance of single-phase leakage 1 kOhm, max: main
protection of 0.07
backup protection - 0,20 operating time of the unit
BKZ-1140 (triggering unit BSO-1140 until the bypass
invalid phase to earth), not more than 0.10 Times since
single-phase leakage of 1.0 kω to ground until the bypass faulted phase on
the earth, with no more than 0,17 maximum inclination of relays in any direction
about a vertical axis, deg, no more than 15 Time to failure, hrs,
less: block BKZ-1140 - 10000 block of BSO-1140 - 10000 block of BSO-1140 when
performing the basic function isolation control and protective switching-off - 20000
Service life, years, not less than 3 Weight, kg, not more than: unit BSO-1140 - 20 unit
BKZ-1140 - 25 Vibration in the place of operation: frequency, Hz from 1 to 35
acceleration, m/S2 up to 5
The compensation device must limit the amount of leakage
electricity up to 50 mA·when the resistance of the single-phase leakage from 1.0
com up to 60% of the resistance of the trigger; when this intermittent current through
the resistance of single-phase leakage of 1.0 kω to bypass the faulted phase on
the ground should not exceed 0.3 A.
Intermittent current through the resistance of single-phase leakage 1,0 kOhm
after bypass faulted phase to earth not more than 0,03 A.
The warranty period shall be 18 months from the date of entry into
operation, but not more than 24 months from date of shipment from the factory. When
the export supply warranty period is 12 months from the date of putting into
operation, but not more than 24 months from the date of crossing the state
border. The relay is built in explosion-proof membrane switchgear
low voltage mine mobile transformer substation voltage
6/1,2 kV with insulated neutral.
General view of the unit BSO-1140 similar General appearance of the block BKZ-1140
(Fig. 1). The unit consists of a casing 1, the removable parts 2 and the bezel 3. On
the side wall of the casing is fixed guides squares and strips for installation
unit in the substation. Removable portion of the block is a chassis on which
mounted circuit elements connected to the front panel wires. On
the front panel has current conducting terminals 4 for external connections
block, and two clamp 5 to the grounding block.
Fig. 1.
General view of the block BKZ-1140, BSO-1140:
1 - casing; 2 - removable part; 3 - front p