Protection apparatus against leakage of current to ground 3 kV azo-3 and voltage of 6 KV azo-6
Price: | negotiated |
Company: | Kompaniya SVITLODAR |
Seller: | Kompaniya SVITLODAR |
Phones: | +38 050 452-32-30 Show phone |
Address: | Ukraine, Dnipropetrovska Oblast' |
The DEVICE is NETWORK-wide PROTECTION against CURRENT LEAKAGE TO EARTH 3 kV AZO-3 , AND a VOLTAGE of 6 KV AZO-6. TU 31.2-00165675-032:2006
The purpose and applications :
The device is intended for
implementation in conjunction with a high voltage cell protective shutoff
the emergence of one-, two - or three-phase leakage current to ground and continuous
control of insulation resistance in the isolated cable networks in mines
hazardous gas and dust, reduce the danger of defeat of people by an electric current
and the probability of explosions of mine gas, fire insulation of electrical equipment
and combustible materials, and prevent premature ignition
electric detonators.
The devices are available in two versions :
- Machine AZO-3
separate operation in cable networks with voltage of 3 kV, powered by
explosion-proof step-down transformers 6/3 kV installed
directly in the mines.
- Machine AZO-6 is designed for
separate operation in cable networks with voltage up to 6 kV supplied from a
explosion-proof separating transformer 6/6 kV installed
directly in the mines, as well as from General industrial dividing transformers
6/6 kV or from separate transformer windings
35/6 - 6 kV, installed on the surface.
Performed function.
The device provides the following functions:
1. Continuous monitoring of insulation resistance of power circuits included
the electrical load;
2. The command to disable the switching apparatus by reducing
resistance earth leakage below the permissible values and the occurrence of leakage
the current to ground;
3. Light alarm activation;
4. Check of serviceability of functioning;
5. Disabling the switching device when disconnecting disconnector or
the extinction of operative voltage;
6. Preventive control of the insulation resistance of the network;
7. Visual inspection of insulation resistance.
8. Continuous self-test apparatus and circuit connection of the midpoint
transformer.
Main parameters and dimensions.
The name of the main parameter and size
The norm
Resistance
tripping single-phase, two-phase and three-phase leakage current to earth
accordingly, kom, not less
for a mains voltage of 6 kV
for a mains voltage of 3 kV
120; 240; 360
60; 120; 180
Current leaks, And no more
0,03
Time actuation of the device when the single-phase leakage resistance of 1 kω and capacitance network from 0.1 to 2 µf per phase, with no more than
0,06
Long the current in the output circuit through a leakage resistance equal to the resistance triggering when a symmetrical three-phase leakage, mA, not more
10
Voltage DC control power (control circuit of the leakage resistance),
450 ±50
Total network capacity, µf per phase, not more
2
Capacity individual plug-in line, µf per phase, not more
1
Nominal voltage single-phase supply frequency (50±1) Hz, V
100
Valid the deviation from the nominal voltage,%
from minus 15
to plus 10
Power consumed by the device at nominal voltage, A, not more
60
Dimensions mm, not more
660 x 850 80 X7
Weight, kg, no more
250,0
Weight of delivery set, kg, not more
280,0