1 The PURPOSE
1.1 Stand stationary high-voltage SVS-100 (in "stand") is intended for
testing the insulation of protective equipment (insulating rod, rubber bots, gloves, tools, etc.,), insulation of power cables and solid dielectrics variables high voltage of industrial frequency, adjustable within 0 - 100kv.
1.2 the Stand is designed for operation under a canopy or in rooms at the operating ambient temperatures from + 5° to + 40° C, relative humidity 80 % at the temperature + 20° C and atmospheric pressure 84,0 - 106,7 kPa (630 - 800 mm RT. Art.).
1.3 To work with the stand requires two operators, with access to work with electrical systems with voltages above 1000 C.
2 TECHNICAL DATA
2.1 Power supply-single-phase AC voltage 220±20 V, frequency 50±2 Hz
2.2 power consumption, not more, VA, - .....................................................500
2.3 Number of sources of high voltage- ....................................................3
2.4 the source Parameters are given in table 2.1
Table 2.1
Option
Source type
BVI-50-1
BVI-50-2
BVI-1
Most the output AC voltage, kV
50
50
1
Most output current, mA
24(when the test mode Gloves and bots)
10 (test mode 3Q)
5 (test mode 100kv)
-
10
Overall dimensions, mm
HH675
HH675
Built-in BOO
Mass, kg
35
35
2.5 Parameters of the test bath:
- number of test electrodes..................................................................4
- overall dimensions (with stand), mm,.............................................. HH
- weight in the dry state, kg, not more.............................................................10
2.6.Given the measurement error built-in meter
voltage, %, not more.........................................................................................3
2.7. Given the measurement error built-in meter
current %, not more...................................................................................................3
2.8. Parameters high-grade measuring current ITR-4:
- limit of measurement (AC), mA, ......................................................10
- given the relative measurement error, %, not more..............................3
2.9. The area occupied device (recommended), m2, ................................................4
2.10.The weight of the equipment, kg, not more,..................................................................... 100
2.11.The service life of equipment apparatus...............................................................10 years
3 COMPOSITION
3.1 Composition and completeness apparatus is presented in table 3.1.
Table 3.1
No.
Name
Col.
Note
1
The control unit
1
2
Block high-voltage testing BVI-50 -1
1
The main block
3
Block high-voltage testing BVI-50 -2
1
For tests 100 kV
4
Meter current high-grade ITR-4
1
5
Charger device for the battery ITR-4
1
6
Lamp signal red
1
7
Switch locking
1
8
Bath for testing insulation bot and gloves included (stand, capacity for water pump, caulking gun, hoses)
1
9
Kit wires and cables for testing
1
10
Stand high voltage inpatient SVS-100.
The user guide. SVS-100/00.00.00.00 re
1
11
Stand high voltage inpatient SVS-100.
The passport. SVS-100/00.00.00.00 PS
1