1.1 Purpose meter
1.1.1 PDS-10 is designed for measurement of the tangent of dielectric loss angle tgδ and capacity of high-voltage insulation With maintenance, repair, adjustment, testing various energy facilities as the place of their install and in the laboratory, as well as for measurement of the tangent of an angle dielectric loss and capacitance of various insulating materials.
1.1.2 PDS-10 produced in responsible the requirements of GOST 22261 for electronic measuring instruments group 4.
1.2 Conditions the operation of the meter
1.2.1 PDS-10 has the following normal conditions of use:
- the ambient air temperature, °C 20±5;
- relative humidity, % 30-50;
- atmospheric pressure, kPa (mm RT. Art.) 84-106 (630-795);
- the power supply frequency, Hz 50±1;
1.2.2 PDS-10 is designed for operation in the following operating conditions applications:
- the ambient air temperature, °C from minus 10 to plus 40;
- relative humidity, % to 90 at 30 °C;
- atmospheric pressure, kPa (mm RT. Art.) 70-106,7 (537-800);
- the power supply frequency, Hz 50±1 or 54±0.2 Hz;
1.2.3 Limiting conditions of transportation:
- the ambient air temperature, °C, from minus 50 to plus 50;
- relative humidity, % to 95 at 30 °C;
- atmospheric pressure, kPa (mm RT. Art.) 70-106,7 (537-800);
- transport shaking:
- the number of beats per minute 80-120;
- maximum acceleration, m/S2 30;
1.2.4 The operation of the product can be made by one operator from among electrical personnel who have studied this document, trained on the practical performance of the product, and having group safety in installations with voltages exceeding 1000 V, not less the third one.
1.3 Technical features
1.3.1 PDS-10 - bridge high-voltage, dual-band meter isolation options. PDS-10 provides a measurement of the tangent of dielectric losses and electrical capacitance. Specifications are given in tables 1 and 2.
Table 1.
The first range ("INPUT1")
-measurement range of tangent of dielectric Peter)
from 50,3;. 10-4 to
-maximum permissible absolute basic error in the measurement of the tangent of dielectric loss angle, for the entire measurement range capacitance at the frequency of the test voltage:
50 Hz
+ (5. 10-4 + 0,05 tgδ)
54 Hz
+ (1. 10-3 + 0,13 tgδ)
-the range measuring the capacitance under test voltage:
10 kV
25 pF to 3000 0 pF;
5 kV
From 50 pF to 60 000 pF;
the permissible error in the measurement of capacity frequency:
50Hz
+ (0.5 pF+0,03 CX);
54 Hz
+ (0.5 pF+0,04 CX);
- operating voltage range
from 1 to 10 kV;
the limit of permissible relative error in the measurement the RMS voltage at a frequency of
50 Hz
+3%;
54 Hz
+3%.
power current through the object of measurement, A2)
from 0 to 0,150
1)the meter converts the tangent of dielectric loss angle, measured at a frequency of 54 Hz to 50 Hz;
2)is shown for reference.