Bizator  /  Adverts  /  equipment and materials  /  power engineering equipment  /  electric power stations equipment

Stand high voltage to burn, acoustic SITA (1st or 2 platforms)

Offer type: salePublished: 28.02.2015
Price:43 500 UAH
Company:OOO PKF Molniya
Seller:Ekaterina
Phones:
Show phone
Write a message
Address:Ukraine, Kharkivs'ka Oblast', Kharkiv
Stand high voltage for the burn acoustic - designed to burn the defective cable insulation; finding the fault location of cable lines acoustic method (works complete with receiver P-806).
1 PURPOSE

1.1. Stand high-voltage SITE is intended for:

  • testing the insulation of cables and other devices and gadgets direct and alternating (50 Hz) high-voltage;
  • burn the defective cable insulation with subsequent ignition thereof;
  • determine the route of cable lines;
  • topographic fault location of cable lines of induction and acoustic methods;
  • determine the distance to the fault of the cables with voltage of 0.4-10 kV pulse bespridelam method for high and low voltage.

1.2. Conditions:

  • the range of ambient temperatures, OS - from minus 20 to +40;
  • relative humidity at 25 ° C - 80 %;
  • atmospheric pressure, mm RT. senior - 650 - 800

1.3. Power SITE is made from industrial single-phase 220V, 50 Hz. Pets powered Autonomous generator of electricity with a capacity of not less than 4.0 kVA. For the full realization of SITE the generator capacity should be not less than 10 kVA.

 

2. TECHNICAL DATA

2.1. the GENERAL TECHNICAL DATA SITE

2.1.1. the Power supply - single-phase alternating current with frequency of 50 is 2 Hz, voltage 220 is 20V

2.1.2. Current consumption, no more, And, 30

2.1.3. Equipment weight, kg, not more than 170

2.1.4. Staff - 2 operator (not less than)

2.1.5. Service life, years 10

 

2.2. The module Manager.

2.2.1. The maximum output voltage in idle mode, kV, 22

2.2.2. The minimum output voltage in idle mode, kV, 1

2.2.3. The number of stages of burning . 5

2.2.4. The maximum current of the unit burn in short circuit mode, And not less than 11

2.2.5. Maximum burning voltage in idle mode,, 500

2.2.6. Maximum afterburning current in short circuit mode, And not less than 22

2.2.7. Power consumption of the unit burning, kW , not more, 16,8

2.2.8. Power consumption, kW, not less than 11

2.2.9. The operation of the burn - long

2.2.10. Weight, kg, not more than 90

2.2.11. Overall dimensions, mm, HH

 

2.3 Module GAUV

2.3.1. The capacity of the drive ratio: 13.5

2.3.2. Maximum output voltage, kV, 18

2.3.3. Maximum discharge pulse energy, j, 2200

2.3.4. Modes of operation:

- manual;

- automatic with pulse repetition rate of discharge of 0.4 Hz

2.3.5. Overall dimensions, mm, HH